15. Add Cables between physical interfaces on the devices
The topology needs to match the logical diagram presented in the
- :ref:`Network Cable Plan <edge_deployment/overview:Network Cable Plan>`.
- Note that many of the management interfaces need to be located either on
- the MGMT or ADMIN VLANs, and the management switch is
+ :ref:`Production Environments <edge_deployment/overview:Production
+ Environments>`. Note that many of the management interfaces need to be
+ located either on the MGMT or ADMIN VLANs, and the management switch is
used to provide that separation.
Rackmount of Equipment
@@ -276,8 +276,9 @@
configuration, so hot air exhaust is out the back of the switch near the
power inlets, away from the 32 QSFP network ports on the front of the switch.
-- The full-depth 1U and 2U Supermicro servers also have front-to-back airflow
- but have most of their ports on the rear of the device.
+- The full-depth servers (such as the 1U and 2U Supermicro servers used in
+ Pronto) also have front-to-back airflow but have most of their ports on the
+ rear of the device.
- Airflow through the rack should be in one direction to avoid heat being
pulled from one device into another. This means that to connect the QSFP
@@ -285,10 +286,9 @@
through the rack from front (switch) to back (server). Empty rack spaces
should be reserved for this purpose.
-- The short-depth management HP Switch and 1U Supermicro servers should be
- mounted on the rear of the rack. They both don't generate an appreciable
- amount of heat, so the airflow direction isn't a significant factor in
- racking them.
+- The short-depth management switches and management servers should be mounted
+ on the rear of the rack. They don't generate an appreciable amount of heat,
+ so the airflow direction isn't a significant factor in racking them.
Inventory
---------